Technical data
44 •  Shielding (Screening) 
 General 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
2.9 Shielding (Screening) 
2.9.1 General 
The shielding of the data and signal conductors reduces electromagnetic inter-
ferences thereby increasing the signal quality. Measurement errors, data trans-
mission errors and even disturbances caused by overvoltage can be avoided. 
Attention 
Constant shielding is absolutely required in order to ensure the technical 
specifications in terms of the measurement accuracy. 
The data and signal conductors should be separated from all high-voltage 
cables. 
The cable shield should be potential. With this, incoming disturbances can be 
easily diverted. 
The shielding should be placed over the entrance of the cabinet or housing in 
order to already repel disturbances at the entrance. 
2.9.2  Bus Conductors 
The shielding of the bus conductor is described in the relevant assembly 
guidelines and standards of the bus system. 
2.9.3 Signal Conductors 
Bus modules for most analog signals along with many of the interface bus 
modules include a connection for the shield. 
Note 
For a better shield performance, the shield should have previously been 
placed over a large area. The WAGO shield connection system is suggested 
for such an application. 
This suggestion is especially applicable if the equipment can have even cur-
rent or high impulse formed currents running through (for example initiated 
by atmospheric discharge). 