3.1.6.2.1 Addressing of Bus Modules 
Addressing first references complex modules (modules that occupy several 
bytes) in accordance with their physical order downstream of the fieldbus con-
troller, i.e., they occupy addresses starting from word 0. 
Following these is the data for the remaining modules, compiled in bytes (mod-
ules that occupy less than one byte). In this process, byte by byte is filled with 
this data in the physical order. As soon as a complete byte is occupied by the 
bit-oriented modules, the process begins automatically with the next byte. 
Note 
For the meaning of input and output bits or bytes of the individual bus mod-
ule please refer to the corresponding bus module description. 
Note 
If a node is changed or expanded, this may result in a new process image 
structure. In this case, the process data addresses also change. In case of an 
expansion, the process data of all previous modules has to be taken into ac-
count. 
Tab. 3-5: Data width for bus modules 
Data width ≥ 1 word (channel):  Data width = 1 bit (channel): 
Analog input modules  Digital input modules 
Analog output modules  Digital output modules 
Input modules for thermocouples  Digital output modules with diagnostics (2 bits/channel) 
Input modules for resistor sensors  Supply modules with fuse carrier/diagnostics 
Pulse width output modules  Solid-state load relays 
Interface modules  Relay output modules 
Up/down counters   
Bus modules for angle and distance measurement   