Technical data
    BACnet/IP Controller 750-830  • 75 
  Data Exchange 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
3.1.6.5.2  Juxtaposition of MODBUS/TCP and IEC 61131-3 Addresses 
3.1.6.5.2.1 Word Access 
Tab. 3-15: Word access 
MODBUS Addresses Method 
decimal  hexadecimal 
IEC 61131 Addresses  Description 
0... 
255 
0x0000 – 
0x00FF 
%IW0... 
%IW255 
phys. inputs (1) 
256... 
511 
0x0100 – 
0x01FF 
%QW256... 
%QW511 
PFC-OUT variables 
512 ... 
767 
0x0200 – 
0x02FF 
%QW0... 
%QW255 
phys. outputs (1) 
768 ... 
1023 
0x0300 – 
0x03FF 
%IW256... 
%IW511 
PFC-IN variables 
illegal address  0x0400 – 
0x0FFF 
not supported   
4096... 
8191 
0x1000 – 
0x1FFF 
not supported  Configuration tab 
8192 ... 
12287 
0x2000 - 
0x2FFF 
not supported  Firmware register 
12288... 
13385 
0x3000 - 
0x3FFF 
%MW0... 
%MW4095 
Flag area (Default: 8 kByte, 
size variable) 
24576 ... 
25340 
0x6000- 
0x62FB 
%IW512... 
%IW1275 
phys. inputs (2) 
FC3 
- Read Multiple Register 
FC4 
– Read Holding Register 
28672 ... 
29436 
0x7000- 
0x72FB 
%QW512... 
%QW1275 
phys. outputs (2) 
0... 
255 
0x0000 – 
0x00FF 
%QW0... 
%QW255 
phys. outputs (1) 
256... 
511 
0x0100 – 
0x01FF 
%IW256... 
%IW511 
PFC-IN variables 
512... 
767 
0x0200 – 
0x02FF 
%QW0... 
%QW255 
phys. outputs (1) 
768 ... 
1023 
0x0300 – 
0x03FF 
%IW256... 
%IW511 
PFC-IN variables 
illegal address  0x0400 – 
0x0FFF 
not supported   
4096... 
8191 
0x1000 – 
0x1FFF 
not supported  Configuration tab 
illegal address  0x2000 - 
0x2FFF 
not supported  Firmware register 
12288... 
16383 
0x3000 - 
0x3FFF 
%MW0... 
%MW4095 
Flag area (Default: 8 kByte, 
size variable) 
24576 ... 
25339 
0x6000- 
0x62FB 
%QW512... 
%QW1275 
phys. outputs (2) 
FC16 
– Write Multiple Register 
28672 ... 
29435 
0x7000- 
0x72F 
%QW512... 
%QW1275 
phys. outputs (2) 