Technical data
76 •  BACnet/IP Controller 750-830 
 Data Exchange 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
3.1.6.5.2.2 Bit Access 
Tab. 3-16: Bit access 
MODBUS Addresses Method 
decimal  hexadecimal 
IEC 61131- 
Addresses 
Description 
0... 
511 
0x0000 – 
0x01FF 
%IX( DigitalOffSet + 0 ).0 ... 
%IX( DigitalOffSet + 31).15 
phys. inputs (1) 
512... 
1023 
0x0200 – 
0x03FF 
%QX( DigitalOffSet + 0 ).0 ... 
%QX( DigitalOffSet + 31).15 
phys. outputs (1) 
Illegal address  0x0400 – 
0x0FFF 
not supported   
4096 … 
8191 
0x1000 – 
0x1FFF 
%QX256.0 ... 
%QX511.15 
PFC-OUT variables 
8192 ... 
12287 
0x2000 – 
0x2FFF 
%IX256.0 ... 
%IX511.15 
PFC-IN variables 
12288 ... 
32767 
0x3000 - 
0x7FFF 
%MX0.0 ... 
%MX1279.15 
Flag area (Default: 8 kByte, 
size variable) 
32768 ... 
34295 
0x8000 - 
0x85F7 
%IX32.0 … 
%IX127.7 
phys. inputs (2) 
FC2 
- Read Input Discrete 
FC1 = FC2 + 0x0200 
– Read Coils 
36864 ... 
38391 
0x9000 - 
0x95F7 
%QX32.0 .. 
%QX127.7 
phys. outputs (2) 
0... 
511 
0x0000 – 
0x01FF 
%QX( DigitalOffSet + 0 ).0 ... 
%QX( DigitalOffSet + 31).15 
512... 
1023 
0x0200 – 
0x03FF 
%QX( DigitalOffSet + 0 ).0 ... 
%QX( DigitalOffSet + 31).15 
phys. outputs (1) 
Illegal address  0x0400 – 
0x0FFF 
not supported   
4096... 
8191 
0x1000 – 
0x1FFF 
%IX256.0 ... 
%IX511.15 
8192... 
12287 
0x2000 – 
0x2FFF 
%IX256.0 ... 
%IX511.15 
PFC-IN variables 
12288... 
32767 
0x3000 - 
0x7FFF 
%MX0.0... 
%MX1279.15 
Flag area (Default: 8 kByte, 
size variable) 
32768... 
34295 
0x8000 - 
0x85F7 
%QX32.0 .. 
%QX1275.15 
FC15- 
- Force Multiple Coils 
36864 ... 
38391 
0x9000 - 
0x95F7 
%QX32.0 .. 
% QX127.7 
phys. outputs (2) 