Technical data
    BACnet/IP Controller 750-830  • 79 
    Fieldbus Node Start-up 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
After a brief period, the 'I/O' LED lights up green, meaning the fieldbus con-
troller is operational. If an error occurred during start-up, an error code is indi-
cated by a red, flashing 'I/O' LED. 
If error code 6 is indicated, followed by error argument 4 by the "I/O" LED af-
ter run-up of the controller with red flashing of error code six times, followed 
by red flashing of the error argument four times, this indicates that an IP ad-
dress has not yet been assigned. 
3.1.7.1.2  Assigning of IP Addresses to Fieldbus Nodes 
The following provides examples of fieldbus node IP address allocation using 
the "WAGO ETHERNET Settings" Program. 
Note 
The program "WAGO-ETHERNET Settings" is available for downloading at 
http://www.wago.com under: Downloads ! AUTOMATION. 
The program is also included on the CD "AUTOMATION Tools and Docs" 
(Item No.: 0888-0412) available from WAGO. 
1. Start the WAGO-ETHERNET Settings program. 
2. Click on Identify to identify the controller connected to the system. 
3.  Select the tab TCP/IP (see Fig. 3-2) 
Fig. 3-2: Setting IP addresses using WAGO ETHERNET Settings  g084906d 
4.  Enter the desired IP Address and, if applicable, the address of the subnet 
mask and gateway. 
5.  Click the button Write to transfer this address to the controller. 
6. Click on Call WBM. An Explorer then opens with the Web-based man-
agement system in which you can make all further settings (see section 
3.1.8.7). 