Technical data
84 •  BACnet/IP Controller 750-830 
  Fieldbus Node Start-up 
 WAGO-I/O-SYSTEM 750 
BACnet/IP Controller 
Note 
It is also possible to assign IP addresses under other operating systems (e.g. 
under Linux) as well as with other BootP servers. 
Note 
The IP address is assigned via straight-through cable, switches, hubs, or via 
direct link using a crossover cable. Addresses cannot be allocated via router. 
3.1.7.2.4.1 BootP Table 
The BootP table is the database for the BootP server. This table is available as 
a text file (bootptab.txt) on the client PC where the WAGO BootP server is in-
stalled. 
Note 
The WAGO BootP server must be installed correctly before the following 
steps can be performed: 
1.  On your PC, go to Start and select the menu item Programs \ WAGO 
Software \ WAGO BootP Server. 
2. Click on WAGO BootP server configuration. 
You are then provided with an editable table "bootptab.txt". 
At the end of the list that highlights possible abbreviations that can be used in 
the BootP table, two examples are given, detailing the allocation of an IP ad-
dress: 
•  "Example of entry with no gateway" 
•  "Example of entry with gateway" 
Fig. 3-12: BootP Table  p012908d 