Technical data
    BACnet/IP Controller 750-830  • 85 
    Fieldbus Node Start-up 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
The examples shown contain the following information: 
Tab. 3-17: BootP Table Information 
Information  Meaning 
node1, node2  Any name for a node can be specified here. 
ht=1  Here the hardware type of the network is specified. 
For ETHERNET the hardware type is 1. 
These numbers are explained in RFC1700. 
ha=0030DE000100 
ha=0030DE000200 
Specify the hardware address (MAC ID) for the BACnet/IP controllers 
here (hexadecimal). 
ip= 10.1.254.100 
ip= 10.1.254.200 
Specify the IP address for the BACnet/IP controller here (decimal) 
T3=0A.01.FE.01  Specify the gateway address here (hexadecimal) 
sm=255.255.0.0  The subnet mask for the subnetwork to which the BACnet/IP controller 
belongs can also be specified here (decimal). 
The local network that is described in this description does not require a gate-
way. You can therefore apply the example "Example of entry with no gate-
way" here. 
3.  In the following text line, replace the 12-place hardware address located 
behind “ha=“ in this example. 
node1:ht=1:ha=0030DE000100:ip=10.1.254.100 
4.  In place of this, enter the MAC address for your own controller. 
5.  If you would like to specify a name for your fieldbus node, delete "node1" 
in the text and enter the node name you wish to use. 
  node1:ht=1:ha=0030DE000100:ip=10.1.254.100 
6.  To assign the controller a specific IP address, mark the IP address given 
here in the example after 
“ip=“ and enter your own IP address. 
node1:ht=1:ha=0030DE000100:ip=10.1.254.100 
7.  Since you do not need the second example "Example of entry with gate-
way" here, place the number sign (#) in front of the text line in Example 
2 as a comment symbol: 
# node2:hat=1:ha=003 0DE 0002 00:ip=10.1.254.200: 
 T3=0A.01.FE.01
This line will not be evaluated after this. 