Technical data
    BACnet/IP Controller 750-830  • 91 
    Programming the PFC Using WAGO-I/O-PRO CAA 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
3.1.8  Programming the PFC Using WAGO-I/O-PRO CAA 
Using IEC 61131-3 programming, the 750-830 BACnet/IP Controller can also 
utilize the function of a PLC in addition to the functions of a fieldbus coupler. 
Creation of an application program in line with IEC 61131-3 is performed us-
ing the programming tool WAGO-I/O-PRO CAA. 
Note 
IEC 61131-3 programming of the controller via ETHERNET requires that the 
check box "CoDeSys" be activated at the Website "Port Configuration" (see 
Section 1.1.8.7). 
You can, however, also connect the client PC and controller serially for pro-
gramming using a programming cable.
A description of programming using WAGO-I/O-PRO CAA is not included in 
this manual. The following sections, on the other hand, contain important in-
formation about creating projects in WAGO-I/O-PRO CAA and about special 
modules that you can use explicitly for programming of BACnet/IP controller. 
Explanations are also provided as to how the IEC 61131-3 program is trans-
ferred and how suitable communication drivers are loaded. 
Additional Information 
For a detailed description of using the software, refer to the manual for the 
"WAGO-I/O-PRO CAA". This manual is located at http://www.wago.com 
under: Documentation ! WAGO-I/O-SYSTEM759 ! WAGO-I/O-PRO ! 
759-333 
1.  Start the programming tool at Start \ Programs \ WAGO-I/O-PRO and 
WAGO-I/O-PRO CAA. 
A dialog window then appears on which you can set the target system for pro-
gramming. 
Fig. 3-4: Dialog window for target system settings  g083005e 
2.  Select the WAGO 750-830 BACnet/IP Controller by entering 
  WAGO_750-830 and then click OK. 
3. Create a new project under File / New. 
4.  In the dialog window that appears select the program type (AWL, KOP, 
FUP, AS, ST or CFC). 