Technical data
    BACnet/IP Controller 750-830  • 93 
    Programming the PFC Using WAGO-I/O-PRO CAA 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
Note 
The number of modules that send or receive data must correspond to the 
existing hardware (except for supply modules, copying modules or end mod-
ules, for example). The number of input and output bits or bytes of the indi-
vidually connected bus modules can be found in the corresponding descrip-
tions of the bus modules. 
Additional Information: 
To obtain further information about an I/O module, either select that module 
from the catalog, or in the current configuration and then click the button 
Data Sheet. The module is then shown in a separate window with its associ-
ated data sheet. 
Note 
For the current version of the data sheets go to http://www.wago.com under 
Documentation. 
8. Click OK to accept the node configuration and close the dialog window. 
The addresses for the control system configuration are then recalculated and 
the tree structure for the configuration updated. 
If required, you can also modify the authorization privileges for individual 
modules if they are to be accessed via fieldbus (MODBUS/TCP/IP). Initially, 
write access from the PLC is defined for each module that is added. Proceed 
as follows to change this setting: 
9. Click on a module in the configuration. 
10. In the right dialog window under the tab 
  "Module parameters" define for each module from where access to the 
module data is to be carried out.  
  You can choose from the following settings in the column "Value" for this: 
•  PLC (standard setting)   -  Access from PFC 
•  MODBUS TCP/UDP   -  Access from MODBUS/TCP 
•  MODBUS RTU     -  Access from MODBUS/RTU 
•  BACnet       -  Access from BACnet/IP 