Technical data
    BACnet/IP Controller 750-830  • 95 
    Programming the PFC Using WAGO-I/O-PRO CAA 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
The file already contains the following syntax: 
 Fig. 3-6: EA-config.xml  P012913x 
The fourth line contains the necessary information for the first bus module. 
The entry MAP=“PLC“ assigns write access privileges to the IEC 61131-3 
program for the first module. 
If you wish to change the access rights, replace "PL" with "FB3" as the access 
privileges from BACnet. 
5. Then complete the fourth line for each individual module using this syntax 
and set the corresponding assigned access privileges: 
<Module ITEMNO=““ MAP=“(e.g..) PLC“ LOC=“ALL“> </Module> 
Note 
It is imperative that the number of line entries matches the number of existing 
hardware modules. 
6. Save the file and reload it to the controller file system via the FTP client. 
You can then begin with IEC 61131-3 programming. 
Additional Information 
For a detailed description of how to use the software, please refer to the 
WAGO-I/O-PRO CAA manual. The manual available at 
http://www.wago.com under Documentation ! WAGO-I/O-SYSTEM 759 
! WAGO-I/O-PRO ! 759-333 