Technical data
    BACnet/IP Controller 750-830  • 99 
    Programming the PFC Using WAGO-I/O-PRO CAA 
WAGO-I/O-SYSTEM 750   
BACnet/IP Controller 
3.1.8.4 General Information about IEC Tasks 
Note 
Please note the following information when programming your IEC tasks. 
•  IEC tasks must have different priorities, as otherwise an error will occur 
during translating of the application program. 
•  An ongoing task may be interrupted by tasks with higher priorities. Execu-
tion of the task that has been interrupted is resumed only when there are no 
other higher-priority tasks to be executed. 
•  If several IEC tasks utilize input or output variables with the same, or over-
lapping addresses in the process image, the values for the input or output 
variables may change while the IEC task is being executed! 
•  Running tasks are halted after each task cycle for a duration that is half the 
time that the task requires (minimum 1 ms). Execution of the task is then 
resumed. 
Example:  1st Task 4 ms ! Waiting period 2 ms 
      2nd Task 2 ms ! Waiting period 1 ms 
•  If no task is incorporated in the task configuration, a freely running default 
task is created internally during the translation. The watchdog for this task 
is deactivated. This task, called "Default task," is recognized by this name 
in the firmware, meaning that the name "Default task" cannot be used for 
other task names. 
•  Sensitivity is of significance only for cyclic tasks. The values 1 and 0 are 
equivalent with regard to sensitivity. A sensitivity value of 0 or 1 results in 
the watchdog event being triggered when the watchdog time is exceeded 
on time. With a sensitivity value of 2, for instance, the watchdog time must 
be exceeded in two consecutive task cycles in order for the watchdog 
event to be triggered. 
•  The following applies to cyclic tasks with watchdog activated: 
If the set, maximum runtime is less than or equal to the call interval, a vio-
lation of the call interval likewise results in the watchdog event being trig-
gered, regardless of the value set for sensitivity. 
•  If the set runtime is greater than the call interval the watchdog event is trig-
gered when the maximum runtime is reached, regardless of the value set 
for sensitivity. 