UL 2703 Recognized Component CDR
Report No. 102066127MPK-003
Quick Mount PV
Page 3 of 35
Issued: 30-Jun-2015
Revised: 27-Feb-2018
2.0 Product Description
Ratings
1. Complete racking system must be grounded and bonded to the required UL 2703.
2. Module frame section meet requirements outlined in illustration No. 2.
3. Installed with evaluated PV module and module level electronic outlined in ratings above.
4. The module frame must be grounded using a UL 2703 listed racking system, e.g. the Quick
Rack rail free racking system from Quick Mount PV. The system is to be installed in
accordance with the latest National Electrical Code, ANSI/NFPA 70, including NEC 250:
Grounding and Bonding, and NEC 690: Solar Photovoltaic Systems. Any local electrical codes
must be adhered in addition to the national electrical codes.
5. System maximum series fuse rating shall not exceed 20 Amps.
Maximum Series Fuse Rating: 20A
Torque for Accessory Frame Bracket: 15 ft-lbs
See section 7.0 illustraction # 1 for a complete list of PV modules and module level power
electronics evaluated with these racking systems
Conditions of
Acceptability
(Typical Conditions of Acceptability to be considered for recognized component products
follow:)
The product covered in this report is not a complete UL 2703 listed racking system. The
Accessory Frame Brackets is intended for use with a UL 2703 listed racking system.
Consideration should be given to the following when the component is used in or with another
ED 16.3.15 (20-Apr-17) Mandatory