QMHSS Engineering Report
Page 1 of 16
March 18
th
, 2015
Mr. Bryan Espiritu Project Number 114490C
QUICKMOUNT PV
2700 Mitchell Dr., Bldg. 2
Walnut Creek, CA 94598
Subject: Laboratory Load Test of the QMHSS with 6061 Base Plate
Dear Mr. Espiritu:
As requested, Applied Materials & Engineering, Inc. (AME) has completed load-testing the QMHSS
hardware. The purpose of our testing was to evaluate the tensile (uplift), compression, and lateral
(perpendicular and parallel to rafter) load capacity of the QMHSS attached to a 2"x4" Douglas Fir rafter
using two 5/16"Ø x 3.5” lag bolts .
SAMPLE DESCRIPTION
Samples were assembled in our laboratory between January 17
th
and January 23
rd
, 2015. Mockup
configuration consisted of three 16" long rafters at 4.5"o.c., screwed to 1/2" Structural I plywood. The
QMHSS is attached through the plywood into a rafter with two 5/16”ø x 3.5” fasteners installed at the
farthest point on the 6061 base plate. QMHSS and 6061 base plate configurations are provided in
Appendix A.
TEST PROCEDURES & RESULTS
1. Compressive Load Test
A total of six tests were conducted for compressive load capacity on January 17
th
, 2015 using a United
Universal testing machine. Samples were rigidly attached to the testing machine and a compressive load
was applied to the hook. The samples were loaded in compression at a constant rate of axial deformation
of 0.09 in. /min. without shock until the hook was bent and came in contact with the test board;
displacement at maximum load was recorded. Based on the above testing, the average maximum
compression load of the QMHSS attached to a 2"x4" Douglas Fir rafter using two 5/16”ø x 3.5” lag
bolts was determined to be 765 lbf. Detailed results are provided in Table I. Test setup and mode of
failure are provided in Appendix B, Figure 1.
The specific gravity and moisture content of the rafters was tested in accordance with ASTM D2395,
Method A (oven-dry). The average specific gravity and moisture content was determined to be 0.454
and 9.2 %, respectively.