TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES April 29, 2016 Quick Mount PV Attn: Amy Rodriguez (email) 2700 Mitchell Drive Walnut Creek, CA 94598 Job No: 11304 Job Name: Quick Mount PV On-Call Lab Testing Walnut Creek, CA Subject: Quick Mount PV Load Testing - Tile Replacement Mount [QMPV# 1-28-2016-Rev C] Ms.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Sample Description (34) 16”x16” wood test boards were delivered to our laboratory on February 26, 2016. Each specimen was made up of 2”x4” lumber, topped with ½” plywood and 30 lb. felt paper. The specimens were equipped with the flashing and 1-1/4” OD by 4-1/2” long post fastened to a 2”x4” Douglas Fir with 4” long, 5/16” diameter GRK RSS Rugged Structural Screws.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Figure 2: Typical Compressive, Lateral, and Resultant Test Board 2118 Rheem Drive, Pleasanton, CA 94588 4770 Duckhorn Drive, Sacramento, CA 95834 One Embarcadero Center, Suite 535, San Francisco, CA 94111 246 30th St.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Structural Test Configurations and Results Tensile (Uplift) Applied Load Figure 3: Tensile Eccentric Load Rafter Test Specific Rafter Peak Deflection Sample L-Foot Gravity Moisture Load at Peak Number at Content [lbs] Load [in] Moisture [%] 1 Unirac 0.536 12.0 1233 3.0585 2 3 4 5 6 7 8 9 10 11 12 Unirac 0.505 Unirac 0.523 Unirac 0.513 Unirac 0.518 Unirac 0.531 Unirac 0.565 Unirac 0.503 Unirac 0.528 Unirac 0.531 Unirac 0.422 Unirac 0.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Photo 1: Tensile Eccentric Load (pre-test) Photo 2: Tensile Eccentric Load (post-test) 2118 Rheem Drive, Pleasanton, CA 94588 4770 Duckhorn Drive, Sacramento, CA 95834 One Embarcadero Center, Suite 535, San Francisco, CA 94111 246 30th St.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Compressive (Downwards with Unirac L-foot) Applied Load Figure 4: Compressive Eccentric Load (shown with Unirac L-foot) Rafter Test Specific Rafter Peak Deflection Sample L-Foot Gravity Moisture Load at Peak Number at Content [lbs] Load [in] Moisture [%] 1 Unirac 0.547 12.1 1096 0.4622 2 Unirac 0.490 12.7 1173 0.5440 3 Unirac 0.498 12.3 1083 0.5363 4 Unirac 0.474 11.7 1241 0.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Photo 3: Compression Eccentric Load (pre-test) Photo 4: Compression Eccentric Load (post-test) 2118 Rheem Drive, Pleasanton, CA 94588 4770 Duckhorn Drive, Sacramento, CA 95834 One Embarcadero Center, Suite 535, San Francisco, CA 94111 246 30th St.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Compressive (Downwards without Unirac L-foot) Applied Load Figure 5: Compressive Eccentric Load (shown without Unirac L-foot) Rafter Test Specific Rafter Peak Deflection Sample L-Foot Gravity Moisture Load at Peak Number at Content [lbs] Load [in] Moisture [%] 1 None 0.520 12.2 2988 0.8160 2 None 0.486 12.2 2799 1.4060 3 None 0.528 11.7 2587 0.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Photo 5: Compressive Eccentric Load (shown without Unirac L-foot, pre-test) Photo 6: Compressive Eccentric Load (shown without Unirac L-foot, post-test) 2118 Rheem Drive, Pleasanton, CA 94588 4770 Duckhorn Drive, Sacramento, CA 95834 One Embarcadero Center, Suite 535, San Francisco, CA 94111 246 30th St.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Lateral (Parallel to Rafter) Applied Load Figure 6: Lateral Parallel to Rafter Eccentric Load Rafter Test Specific Rafter Peak Deflection Sample L-Foot Gravity Moisture Load at Peak Number at Content [lbs] Load [in] Moisture [%] 1 2 3 4 Unirac 0.500 Unirac 0.531 Unirac 0.514 Unirac 0.457 Average 11.6 12.1 12.5 12.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Photo 7: Lateral Parallel to Rafter Eccentric Load (pre-test) Photo 8: Lateral Parallel to Rafter Eccentric Load (post-test) 2118 Rheem Drive, Pleasanton, CA 94588 4770 Duckhorn Drive, Sacramento, CA 95834 One Embarcadero Center, Suite 535, San Francisco, CA 94111 246 30th St.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Lateral (Perpendicular to rafter) Applied Load Figure 7: Lateral Perpendicular to Rafter Eccentric Load Rafter Test Specific Rafter Peak Deflection Sample L-Foot Gravity Moisture Load at Peak Number at Content [lbs] Load [in] Moisture [%] 1 Unirac 0.500 12.3 351 1.3575 2 Unirac 0.508 11.8 360 3 4 5 6 2.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Photo 9: Lateral Perpendicular to Rafter Eccentric Load (pre-test) Photo 10: Lateral Perpendicular to Rafter Eccentric Load (post-test) 2118 Rheem Drive, Pleasanton, CA 94588 4770 Duckhorn Drive, Sacramento, CA 95834 One Embarcadero Center, Suite 535, San Francisco, CA 94111 246 30th St.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Resultant Load at 6:12 Roof Slope/Pitch 6 Applied Resultant Load at 6:12 Slope 12 Figure 8: Resultant 6:12 Eccentric Load (Downslope) Rafter Test Specific Rafter Peak Deflection Sample L-Foot Gravity Moisture Load at Peak Number at Content [lbs] Load [in] Moisture [%] 1 Unirac 0.487 12.5 441 1.3365 2 Unirac 0.506 11.8 436 1.2139 3 Unirac 0.547 11.3 433 1.1209 4 Unirac 0.500 11.0 446 1.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Photo 11: Resultant 6:12 Eccentric Load (Downslope, pre-test) Photo 12: Resultant 6:12 Eccentric Load (Downslope, post-test) 2118 Rheem Drive, Pleasanton, CA 94588 4770 Duckhorn Drive, Sacramento, CA 95834 One Embarcadero Center, Suite 535, San Francisco, CA 94111 246 30th St.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES 6 12 Applied Resultant Load at 6:12 Slope Figure 9: Resultant 6:12 Eccentric Load (Upslope) Rafter Test Specific Rafter Peak Deflection Sample L-Foot Gravity Moisture Load at Peak Number at Content [lbs] Load [in] Moisture [%] 1 Unirac 0.472 12.4 1845 1.5212 2 Unirac 0.436 11.8 1917 1.0633 3 Unirac 0.472 12.4 1815 1.6158 4 Unirac 0.515 11.1 1946 1.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Photo 13: Resultant 6:12 Eccentric Load (Upslope, pre-test) Photo 14: Resultant 6:12 Eccentric Load (Upslope, post-test) 2118 Rheem Drive, Pleasanton, CA 94588 4770 Duckhorn Drive, Sacramento, CA 95834 One Embarcadero Center, Suite 535, San Francisco, CA 94111 246 30th St.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Installation Drawings Figure 10a: Installation Drawing 2118 Rheem Drive, Pleasanton, CA 94588 4770 Duckhorn Drive, Sacramento, CA 95834 One Embarcadero Center, Suite 535, San Francisco, CA 94111 246 30th St.
TESTING INSPECTION ENGINEERING CONSTRUCTION TESTING SERVICES Figure 10b: Installation Drawing Limitations: Testing was conducted in general accordance with industry standard testing procedures, including ASTM D1761-12, D2395-14, and ICC AC13. The data provided is the result of those tests. CTS assumes no liability and makes no warranty, or implied, y, expressed p p , as to the usefulness of any information, product, apparatus, or process disclosed.