Installation Guide

Quiet Walls
2/2019
Keep fasteners as flush as possible, since all protrusions will put a dimple into the
finished wallboard. Fasteners shall not protrude more than 1/16” from Quiet Walls
surface.
Tightly butt the side of the next sheet of Quiet Walls to the edge of the attached
sheet. Do not overlap seams;
Tape all seams with Acrylic tape or equivalent. The tape is semi-permanent, and
will be permanently sealed in position when drywall is hung.
o If Quiet Walls is installed horizontally or a seam does not fall on a stud the
seams must be taped preferably with Acrylic tape which provides a long
lasting attachment.
o If seams fall on the stud, with no gaps >1/8”, no taping is required. Drywall
installation will seal the Quiet Walls against the existing studs.
o Commercial Alternatives include commercial duct tape
Quiet Walls is easily cut to fit around irregular objects and electrical boxes. The
material should be cut around outlets, switches, and junction boxes. Gaps shall be
less 1/8”. If greater, they shall be sealed with acoustical caulk.
Putty pads should be installed on the back of all electrical boxes;
Caulk the bottom plate at the floor line with acoustical sealant;
Install drywall per normal technique (ASTM# C840 – Standard Specification for
Application and Finishing of Gypsum Board). dB-3 will be fastened permanently
when the gypsum board is hung.