Technical information
www.quietside.com
11
AQN36VFUAGM Heat Pump Mini Split
Indoor Unit : AQN36VFUAGM Outdoor Unit : AQX36VFUAGM
Power
Power Voltage :
208/230V – 1 Ph – 60 Hz
Control Voltage :
DDC Fuzzy Logic
Main Breaker Size :
30 A
Line Sizes :
“Liquid” (expanded gas) line
1/4”
Suction
5/8”
BOTH LINES MUST BE INSULATED SEPARATELY
Interconnect Length
Maximum / Minimum Length
164 / 10 feet
Vertical lift
98 feet (Trap required at 26ft)
(Note condenser can be above or below evaporator)
Charging
Unit is charged for
25 ft (Factory Charge 88.1oz R410A)
Additional Charge of R410A
0.43oz/ft over 25ft
Charge for Line Run lengths
Length
25
35
45
55
65
75
85
95
100
Added Charge (oz)
0
4.3
8.6
12.9
17.2
21.5
25.8
30.1
32.25
Interconnecting Wiring
Gauge
14 AWG Power &16 AWG Shielded Communication
Number of Interconnecting Wires
3x14 AWG Power & 2x16 AWG Control = 5 Total