Technical information
www.quietside.com 
19 
EH Model Series Rotary Switch Settings 
Indoor unit Dip Switch Settings - EH Model Series 
The correct setting of the Indoor PCB Dip Switches and the Dip Switches is required 
Indoor Unit Dip Switches are all set in the ON position as the Factory Default 
Depending on the application certain switches must be set to the OFF position to 
allow use of an option, or specific control feature 
USE OF THE WIRED REMOTE CONTROL IS STANDARD, THE #1 DIP SWITCH ON SW05 
OF THE MAIN PCB OF THE INDOOR UNIT MUST BE SWITCHED TO THE OFF POSITION BEFORE 
STARTING THE UNIT 
Samsung recommend altering Dip switches prior to mounting the Indoor unit 
Switch #'s read Left to Right, count to ensure the correct one is switched as they are all labeled 1-4 
Indoor Unit 
Switch# 
Controls 
Action 
Setting 
SW05 
1 
Use of Wired Remote 
Switch to OFF if Wired Remote is used 
OFF 
2 
Central Control/SNET 
Switch to OFF if Central/SNET option is used 
ON 
3 
Not used on this unit 
Ignore 
ON 
4 
Condensate Pump 
Switch to OFF if Samsung Pump is installed 
ON 
SW06 
1 
Temp Compensation 
Switch to OFF to compensate for duct heat gain 
ON 
2 
Filter Timer Light 
Switch to OFF to increase time for filter change 
ON 
3 
Hot Water Coil 
Contact Factory to discuss auxiliary heat option 
ON 
4 
Not used on this unit 
Ignore 
ON 
SW07 
1 
Not used on this unit 
Ignore 
ON 
2 
Not used on this unit 
Ignore 
ON 
3 
Remote On/Off control 
Switch to OFF to allow external control of unit 
ON 
4 
Not used on this unit 
Ignore 
ON 
MWR-TH01 Wired Remote Control 
K1 
Heat Pump/Cooling Only 
Switch to ON for Heat Pump operation 
ON 
K2 
Use of F3/F4 or F1/F2 
Switch to OFF as unit uses F3 - F4 Comms  
OFF 
K3 
Display DegC or DegF 
Switch to ON for DegF Display 
ON 
K4 
Wired/Wireless Control 
Switch to OFF to allow use of both controls 
ON 
K5 
Not used on this unit 
Ignore 
N/A 
K6 
Not used on this unit 
Ignore 
N/A 
K7 
Not used on this unit 
Ignore 
N/A 
K8 
Not used on this unit 
Ignore 
N/A 
After every Dip Switch change the power to the system must be turned off for 3 minutes 
to allow the unit to recognize the changes to the Dip Switch settings 