Technical information
www.quietside.com 
20 
DH105CAV MSP Duct Heat Pump 
Indoor Unit : DH105CAV Wired Remote : MWR-WE10 Outdoor Unit : UH105CAV 
Power 
Power Voltage : 
208/230V – 1 Ph – 60 Hz 
Control Voltage : 
DDC Fuzzy Logic 
Main Breaker Size : 
35 A 
Line Sizes :  
“Liquid” (expanded gas) line 
3/8” 
Suction 
5/8” 
BOTH LINES MUST BE INSULATED SEPARATELY    
Interconnect Length 
Maximum / Minimum Length 
246 / 10 feet 
Vertical lift 
98 feet (Trap required every 50ft) 
(Note condenser can be above or below evaporator) 
Charging   
Unit is charged for 
25 ft (Factory Charge 98.8oz R410A) 
Additional Charge of R410A 
0.4oz per ft over 25ft 
Charge for Line Run lengths 
Length 
25 
45 
65 
85 
105 
125 
150 
175 
200 
Added Charge (oz) 
0 
8.0 
18.0 
24.0 
32.0 
40.0 
50.0 
60.0 
70.0 
Interconnecting Wiring 
Gauge 
14 AWG Power &16 AWG Shielded Communication 
Number of Interconnecting Wires 
3x14 AWG Power & 2x16 AWG Coms = 5 Total 
Between unit and Wired RMC 
2 sets of 2x16 AWG Control, for 12VDC Power, Coms 
Indoor Unit Outdoor Unit
(Ground) F2 F2 Separate all Power
F1 F1 & Communications
Wiring by 2" 
G G
2(N) 2(N)
1(L) 1(L)
L Power Supply is 208/230V
F4 N even though L & N is used 
F3 for Terminal designation
V2
V1 208/230V
System 
Breaker
Wired Remote
Controller
V2
F3
F4
V1