Technical information
www.quietside.com 
23 
 CH070CAV1 Cassette Heat Pump 
Indoor Unit : CH070CAV1 Wired Remote : MWR-WE10 Outdoor Unit : UH070CAV1 
Power 
Power Voltage : 
208/230V – 1 Ph – 60 Hz 
Control Voltage : 
DC Fuzzy Logic 
Main Breaker Size : 
25 A 
Line Sizes :  
“Liquid” (expanded gas) line 
1/4” 
Suction 
5/8” 
BOTH LINES MUST BE INSULATED SEPARATELY    
Interconnect Length 
Maximum / Minimum Length 
162 / 10 feet 
Vertical lift 
98 feet (Trap required every 26ft) 
(Note condenser can be above or below evaporator) 
Charging   
Unit is charged for 
25 ft (Factory Charge 67oz R410A) 
Additional Charge of R410A 
0.1oz per ft over 25ft 
Charge for Line Run lengths 
Length 
25 
40 
55 
70 
85 
100 
115 
130 
150 
Added Charge (oz) 
0 
1.0 
2.0 
3.0 
4.0 
5.0 
6.0 
7.0 
8.0 
Interconnecting Wiring 
Gauge 
14 AWG Power &16 AWG Shielded Communication 
Number of Interconnecting Wires 
3x14 AWG Power & 2x16 AWG Comms = 5 Total 
Between unit and Wired RMC 
4x16 AWG Control, 2 for 12V DC Power, 2 Comms 
Indoor Unit Outdoor Unit
(Ground) F2 F2 Separate all Power
F1 F1 & Communications
Wiring by 2" 
G G
2(N) 2(N)
1(L) 1(L)
L Power Supply is 208/230V
F4 N even though L & N is used 
F3 for Terminal designation
V2
V1 208/230V
System 
Breaker
Wired Remote
Controller
V2
F3
F4
V1