CH Model Series Rotary Switch Settings 
Indoor unit Dip Switch Settings - DH Model Series 
The correct setting of the Indoor PCB Dip Switches and the Dip Switches is required 
Indoor Unit Dip Switches are all set in the ON position as the Factory Default 
Depending on the application certain switches must be set to the OFF position to 
allow use of an option, or specific control feature 
USE OF THE WIRED REMOTE CONTROL IS STANDARD, THE #1 DIP SWITCH ON SW05 
OF THE MAIN PCB OF THE INDOOR UNIT MUST BE SWITCHED TO THE OFF POSITION BEFORE STARTING THE UNIT 
Samsung recommend altering Dip switches prior to mounting the Indoor unit 
Switch #'s read Left to Right, count to ensure the correct one is switched as they are all labeled 1-4 
Indoor Unit 
Switch# 
Controls 
Action 
Setting 
SW05 
1 
Use of Wired Remote 
Switch to OFF if Wired Remote is used 
OFF 
2 
Central Control/SNET 
Switch to OFF if Central/SNET option is used 
ON 
3 
Not used on this unit 
Ignore 
ON 
4 
Condensate Pump 
Ignore - Condensate Pump is standard on CH Units 
N/A 
SW06 
1 
Temp Compensation 
Switch to OFF to compensate for duct heat gain 
ON 
2 
Filter Timer Light 
Switch to OFF to increase time for filter change 
ON 
3 
Not used on this unit 
Ignore 
ON 
4 
Not used on this unit 
Ignore 
ON 
SW07 
1 
Minimum EEV Step 
Switch to OFF to close EEV completely in off cycle 
ON 
2 
Master/Slave 
Switch to OFF to designate Master 
ON 
3 
Remote On/Off control 
Switch to OFF to allow external control of unit 
ON 
4 
Not used on this unit 
Ignore 
N/A 
E620 error on start up of MWR-WE10 
"E620" indicates the wired controller has a different temperature unit setting than the indoor unit. 
The following steps will set the controller to degF and enable it to communicate with the indoor unit. 
Press and hold the "SET" and "ESC" buttons for at least 3 seconds. A flashing "1" will display (main menu) 
Press (>) button – another “1” will display & flash for the sub menu 
Press (>) button again to display the 4 digit “data settings” 
"0100" should be displayed for the “data settings” 
Press the (>) until the 4th digit is flashing in the "data bit field". 
Press the (v) button to change that digit to “1” 
"0101" should now be displayed for "data setting" 
Press the “SET” button, then press “ESC” 