Technical information

www.quietside.com
27
MH050FXCA2A Dual Zone Heat Pump
Outdoor Unit
Matching Indoor units: MH026FNCA, MH026FECA, MH035FNCA, MH035FECA, NJ030MHXCA,
NJ035MHXCA, NJ0261HXCA & NJ0351HXCA
Power
Power Voltage :
208/230V 1 Ph 60 Hz
Control Voltage :
DC Fuzzy Logic
Main Breaker Size :
25 A
Line Sizes :
“Liquid” (expanded gas) line
1/4
Suction
3/8”
ALL LINES MUST BE INSULATED SEPARATELY
Interconnect Length
Maximum Combined Length
Maximum / Minimum Individual Length
Vertical lift
(Note condenser can be above or below evaporator)
Charging
Unit is charged for
65 ft (Factory Charge 70.55oz R410A)
Additional Charge of R410A
0.11oz/ft over 65ft
Charge for Combined Line Run lengths
Length
25
35
45
55
65
75
85
95
100
Added Charge (oz)
0
0
0
0
0
1.1
2.2
3.3
3.9
Interconnecting Wiring
Gauge
14 AWG Power, 1(L), 2(N) & 16 AWG Shielded Communication, F1, F2
Number of Interconnecting Wires
3x14 AWG Power & 2x16 AWG Control = 5 Total