Technical information

www.quietside.com
28
MH080FXCA4A Quad Zone Heat Pump
Outdoor Unit
Matching Indoor units: MH026FNCA, MH026FECA, MH035FNCA, MH035FECA, MH052FNCA,
MH052FECA, NJ030MHXCA, NJ035MHXCA, NJ052MHXCA, NJ0261HXCA & NJ0351HXCA
Power
Power Voltage :
208/230V 1 Ph 60 Hz
Control Voltage :
DC Fuzzy Logic
Main Breaker Size :
25 A
Line Sizes :
“Liquid” (expanded gas) line
1/4
Suction
(MH026 & MH035) 3/8”
(MH052) 1/2”
ALL LINES MUST BE INSULATED SEPARATELY
Interconnect Length
Maximum Combined Length
Maximum / Minimum Individual Length
Vertical lift
(Note condenser can be above or below evaporator)
Charging
Unit is charged for
131 ft (Factory Charge 98.77oz R410A)
Additional Charge of R410A
0.11oz/ft over 131ft
Charge for Combined Line Run lengths
Length
25
45
65
85
105
131
150
175
200
Added Charge (oz)
0
0
0
0
0
0
2.1
4.8
5.6
Interconnecting Wiring
Gauge
14 AWG Power, 1(L), 2(N) & 16 AWG Shielded Communication, F1, F2
Number of Interconnecting Wires
3x14 AWG Power & 2x16 AWG Control = 5 Total