Technical information
www.quietside.com 
3 
AR09HSFSHWKNCV Heat Pump Mini Split 
Indoor Unit : AR09HSFSHWKNCV    Outdoor Unit : AR09HSFSHWKXCV 
Power 
Power Voltage : 
208/230V – 1 Ph – 60 Hz 
Control Voltage : 
DDC Fuzzy Logic 
Main Breaker Size : 
15 A 
Line Sizes :  
“Liquid” (expanded gas) line 
1/4” 
Suction 
3/8” 
BOTH LINES MUST BE INSULATED SEPARATELY    
Interconnect Length 
Maximum / Minimum Length 
50 / 10 feet 
Vertical lift 
26 feet 
(Note condenser can be above or below evaporator) 
Charging   
Unit is charged for 
25 ft (Factory Charge 44.1oz R410A) 
Additional Charge of R410A 
0.16oz/ft over 25ft 
Charge for Line Run lengths 
Length 
25 
35 
45 
50 
Added Charge (oz) 
0 
1.6 
3.3 
4.0 
Interconnecting Wiring 
Gauge 
14 AWG Power &16 AWG Shielded Communication 
Number of Interconnecting Wires 
3x14 AWG Power & 2x16 AWG Control = 5 Total 