Technical information

www.quietside.com
9
AQN18VFUAGM Heat Pump Mini Split
Indoor Unit : AQN18VFUAGM Outdoor Unit : AQX18VFUAGM
Power
Power Voltage :
208/230V 1 Ph 60 Hz
Control Voltage :
DDC Fuzzy Logic
Main Breaker Size :
15 A
Line Sizes :
“Liquid” (expanded gas) line
1/4
Suction
1/2
BOTH LINES MUST BE INSULATED SEPARATELY
Interconnect Length
Maximum / Minimum Length
Vertical lift
(Note condenser can be above or below evaporator)
Charging
Unit is charged for
25 ft (Factory Charge 45.8oz R410A)
Additional Charge of R410A
0.16oz/ft over 25ft
Charge for Line Run lengths
Length
25
35
45
55
65
75
85
95
98
Added Charge (oz)
0
1.6
3.2
4.8
6.4
8.0
9.6
11.2
11.68
Interconnecting Wiring
Gauge
14 AWG Power &16 AWG Shielded Communication
Number of Interconnecting Wires
3x14 AWG Power & 2x16 AWG Control = 5 Total