Instruction manual
55
Section 8 – Troubleshooting
FAILURE TO START
PROBABLE CAUSE CORRECTION
Power not turned "ON" Turn the power "ON" by closing the main disconnect switch
or circuit breaker.
Blown control circuit fuse Replace fuse. Find and correct cause.
Safety circuit shutdown resulting
from high discharge air temperature
Correct the situation in accordance with the instruction in the
"High Discharge Air Temperature and/or High Fluid Injection
Temperature" section of this troubleshooting guide. Restart
the vacuum pump.
Thermal overload relays tripping Correct the cause of the overloaded condition, reset overload
relay and press the start button.
Low voltage Ask the power company to make a voltage check at your
entrance meter, then compare that reading to a reading taken
at the motor terminals. Use these two readings as a basis for
locating the source of low voltage.
Faulty start switch Check the switch for malfunction or loose connections.
Faulty control relay Replace the relay.
Loose wire connections Check all wiring terminals for contact and tightness.
Faulty High Air Temperature Switch Check HAT switch. Contact a qualified service technician
for repairs.
Faulty transformer Check secondary voltage on transformer.










