Installation manual

RIVA PLUS COMBI MANUAL 25
12. F PVC boiler adapter
Figure 9.5
This kit is required to vent the Riva boiler using PVC/CPVC pipe. The kit includes a boiler
connection adapted for PVC/CPVC. When venting with PVC/CPVC this boiler adapter is
required in addition to one of the terminations on the following pages.
Canada: All PVC/CPVC pipe, ttings, and cement must be approved to ULC S636. Do
not mix pipe and joining compounds from different manufacturers as this can
result in an unsafe condition and void the certication.
Installation:
Attach the collar (C) from the adapter kit to the top of the boiler using the supplied screws.
Insert the boiler adapter (B) into the collar. Check that the exhaust gasket (D) is installed on
the outlet of the boiler rst.
Once the adapter is positioned in place, tighten the clamp on the collar and install the
supplied self tapping screw through the pre drilled hole on the collar.
Insert the PVC adapters (A) into the boiler adapter (B).
Slide the CPVC/PVC pipe into the PVC adapters (A), do not use any solvents or cement on
this connection. It is a gasket connection that requires no sealing.