Installation manual
34 RIVA PLUS COMBI MANUAL
12. Electrical Connections/Wiring Cont.
12.7 Installing the outdoor reset temperature probe:
The outdoor reset temperature probe must be installed on an external wall of the building,
avoiding:
• Direct sun radiation.
• Wet walls or walls where mould tends to form.
• Installation near fans, exhaust or chimney vents.
When connecting the outdoor reset temper-
ature probe to the boiler, use electric wires
with a minimum 20 AWG (0.032 in DIA).
The electric wires for connecting the
outdoor reset temperature probe to the
boiler must run through different conduit
than line (120 VAC), as they are powered
at a low safety voltage and the maximum
length must not exceed 65 feet.
• Remove the two screws shown in Figure
12.12 and open the outdoor reset con-
nection terminal board.
12.8 Electric connection between the boiler and the outdoor reset temperature probe:
Figure 12.12
• Connect the two electric wires to termi-
nals E1 and E2 on the terminal board as
shown in Figure 12.13.
• Connect the same wires to the external
probe terminals
Figure 12.13
Outdoor reset
probe connection
terminal board
TO THE OUTDOOR RESET
TEMPERATURE PROBE
The path of the outdoor reset temperature
probe wires or cable must follow the indicat-
ed path and be fastened as shown in Figure
12.14.
Figure 12.14
to the room
thermostat
to the service
switch
to the
outdoor rese
t
temperature
probe