RIVA PLUS COMBI MANUAL 45
15. Commissioning Cont.
Useful output
KW 15 16.8 18.5 20.5 22 23.8 26 28
BTU/h 51225 58055 63177 70005 75130 81277 88790 95620
Natural
Pa
inwc.
290
1.16
370
1.48
460
1.84
560
2.24
660
2.65
780
3.13
900
3.61
1040
4.17
m³/h
ft³/h
1.76
5.77
2.00
6.56
2.23
7.31
2.46
8.07
2.69
8.82
2.91
9.54
3.14
10.30
3.36
11.02
Propane
Pa
inwc.
680
1.45
860
1.69
1060
2.25
1270
3.21
1500
4.34
1740
5.62
2000
7.06
2270
8.95
Kg/h
lb/h
1.3
3.0
1.5
3.3
1.7
3.7
1.9
4.1
2.0
4.4
2.2
4.8
2.3
5.1
2.5
5.5
Table 15.1
15.10 Labels placement:
Figure 15.11
1
4
2
3
5
15.9 Adjustment of the useful c.h. output:
Turn the boiler OFF.
Open the gas valve outlet pressure test point 15 (gure 15.4) and connect the gauge.
Turn the boiler ON positioning the function selector B in the position shown in gure 15.6
and ensure that the room thermostat is set to “heat demand”.
Loosen screws D and remove the service panel (gure 15.7).
To carry out the adjustment use the adjustment device (RISC) with the help of a screwdriver.
By rotating the device clockwise the pressure increases.
Adjust the gas pressure at the burner to the value according to the useful c.h. output wanted (Tab. 15.1).
Reassemble the service panel.
Close the gas valve outlet pressure test point 15 (gure 15.4).
Reassemble the front panel of the case.