Cut Sheet
513.204.6060 or 800.543.4936 • www.rke.com
Part number includes
socket and holddown.
2/4/13
Ordering Information
Universal Function
Relay
Specications
Electrical
Supply Voltage: 24 to 240VAC/VDC
Frequency: 50 to 400Hz
Prox Supply: 15 mAmps @ 12VDC
Frequency Range: 0.1 to 200PPS
Sensor Type: Prox or Contact
Signal Input: Sourcing (PNP)
Pick-Up/Drop-Out Delay: 0.5 Sec
Time Ranges: 0.1Sec. up to 24 Hrs.
Remote Pot: 1KΩ to 20KΩ (Max.)
Power Consumption: 1.5VA
Indicators: 2 LEDs
Operations
The TDR series of electronic relays
is a processor based control that can
have many different functions. The
operation of the TDR is determined at
the time of manufacture, based on the
rmware loaded into the relay.
Special functions (X) that are unique
to a customer’s specic application
are available by contacting the factory.
Functions available include:
C - On Delay (Delays to turn On)
D - Interval On (Turns On and then
times out)
F - Off Delay (Turns on then delay
turning Off after loss of signal)
L - Pulse Frequency (Supplies prox
power on monitors pulse frequency)
R - Repeat Cycle (On & Off & On &
Off etc.)
S - One Shot (One output per input)
U - Universal (Multiple functions and
time ranges)
•24to240VAC/VDC
(Universal Voltage)
•MultipleFunctons
•Timerangesupto24
hours
•PulseFrequencies
•AdjustmentKnobs
•Plug-InPackage
•DPDTContacts
•StatusLEDs
Output Rating @ 25°C:
5 Amps @ 250VAC (General Purpose)
1/8 HP @ 120VAC
5 Amps @ 30VDC
B300 (Pilot Duty)
360 VA
3 Amps @ 120VAC
1.5 Amps @ 240VAC
Physical
Mounting:Plug-In
Termination: 8 or 11Pin
Packaging: Dust Cover
Weight: 8.5 Oz. Approx.
AmbientTemperatures
Operating: 0°C to 65°C
Storage: -40°C to 85°C
Dimensions
Connections
These are general connections. See
specic function sheets for complete
connection diagrams.
Listed
42L2
Function
C - On Delay
D - Interval On
F - Off Delay
L - Pulse Frequency
R - Repeat Cycle
S - One Shot
U - Universal Timer
X - Special
Adjustment
A - Adjustable
F - Fixed
R - Remote
X - Special
TDR-24/240V-AC8-
R-KModel
Option
XXXX
TDR
.6" 1.8"
2.3"
3.6"
Voltage
24/240V - 24-240VAC/VDC
Pin Base
8 - 8 Pin Base
11 - 11 Pin Base
1
2
3
45
6
7
8
Functions:
C, D, R & U
Supply
1
2
3
45
6
7
8
Function: L
+ Pwr
+ Sig
- Com
Supply
1
2
3
45
6
7
8
Functions:
C, D, R & U
Remote Adj.
Supply
Remote
Pot
1
2
3
4
5
6
7
8
9
10
11
Functions:
C, D, R & U
Remote Adj.
Remote
Pot
Supply
Functions: F & S
1
2
3
4
5
6
7
8
9
10
11
Initiate
Contact
Initiate
Voltage
Supply