The digital  input  terminals 
on both models 
DANGER 
THE MOTOR TERMINALS (U, V, W / T1, T2, T3) AND BRAKING RESISTOR 
TERMINALS (R+ AND R- WHEN APPLICABLE) ARE LIVE WHEN THE 
FREQUENCY CONVERTER IS CONNECTED TO A MAINS SUPPLY, EVEN WHEN 
THE MOTOR IS NOT RUNNING. THE CONTROL BOARD’S RELAY OUTPUT 
TERMINALS (WHEN APPLICABLE) MAY HAVE A DANGEROUS CONTROL 
VOLTAGE, EVEN WHEN THE FREQUENCY CONVERTER IS DISCONNECTED 
FROM THE MAINS SUPPLY. THESE CONDITIONS MAKE A RISK OF 
ELECTRICAL SHOCK POSSIBLE. 
WARNING 
The RCD current from the frequency converter can exceed 3.5mA AC. 
According to standard EN61800-5-1, a reinforced protective ground connection 
shall be ensured to reduce the risk of an electrical shock. 
4.3.4  Conductor diameter and stripping lengths 
Use cables with heat resistance of at least 70°C. 
4.3.5  Recommended tightening torques 
The screw tightening torques of the power module terminals are 0.5 – 0.6 Nm and for control board’s digital input 
terminals 0.5 Nm. 
Note: Do not over tighten the terminal screws. Over tightening can cause the terminal block to break. If the terminal block 
breaks, the entire frequency converter must be replaced. 