5.2.5  S7 Current Limit in traveling movement application 
The  frequency  converter  limits  the  maximum  current.  The  limit  settings  for  different  currents  are  shown  in  the 
following table. The limit is a percentage of the device’s nominal current. 
Frequency converter 
model 
Nominal current [A] 
003  2.4 
006  5.6 
Switch S7 
Current 
Limit [%] 
003 [A] 
006 
[A] 
Motor Example 
-1  -2  -3  003  006 
0  1  0  150 % (*)  3.6  7.7  2 x MF06MA200 
2 x MF06LA200, 
2 x MF06LA100, 
4 x MF06MA200 
1  1  1  130 %  3.1  6.6     
1  1  0  120 %  2.9  6.1     
0  0  0  110 %  2.6  5.6  MF06LA200   
1  0  1  100 %  2.4  5.1     
0  0  1  90 %  2.2  4.6  MF06MA200 
2 x MF06MA200, 
MF06LA200, MF06LA100 
1  0  0  80 %  1.9  4.1     
0  1  1  70 %  1.7  3.6  MF06MK200 35Hz  MF06MA200 
(*) Factory default setting. 