5.2.8  S4 Control method and slowdown mode in traveling movement application 
The frequency converter can be parametrised for two different control methods. The control method options are 
listed in the following table. The descriptions of the control methods are given in the section “Control methods”. 
Digital inputs and the control method: 
Terminal 
Name  MS2  EP2 
1 
DI1  S1  S1 
2 
DI2  S2  S2 
3 
DI3  MS2  AP 
4 
DI4  S11/S21  S11/S21 
5 
DI5 *)  S12/S22  S12/S22 
6 
DI6  ES  ES 
*) Note: As factory default DI5 is not in use. The stop limit signal shall be connected in series to direction signals 
respectively. 
Control signals: 
S1  Drive command forward 
S2  Drive command reverse 
MS2  Multistep 2 frequency 
AP  Acceleration command 
S11  Slowdown limit forward 
S12  Stop limit forward 
S21  Slowdown limit reverse 
S22  Stop limit reverse 
ES  External stop, used for thermal protection of the motor 
Switch S4 - 1  Control method 
0  EP2 
1  MS2 
The switch model has one slowdown input DI4. There are two ways to handle the slowdown command and the 
selection is made with  switch S4-2. Alternatives are shown  in the following table.  As the slowdown limit  switch 
contact opens during running, the maximum speed is limited in the running direction. 