The  warning  and  fault  code  numbers  and  corresponding  warnings  and  faults,  possible  causes  and  suggested 
solutions are listed in the following table. 
  Code  Warning or Fault  Possible cause  Solution 
  1 
Over current / current 
limit (stall) 
•  A sudden and significant load increase 
has occurred 
•  There is a short circuit in the motor cable 
•  The motor is inadequate for the 
application 
•  The motor parameters have been set 
wrong 
•  Current limit activates 
•  Ramp time is too short 
•  Check the load of the motor 
•  Check the motor brake operation 
•  Check the connection of the motor cable 
•  Check the motor insulation 
•  Verify the correct parameters 
•  Check crane/trolley runway clearness 
To reset: Power off and restart after 1 min. 
  2 
Power supply under- or 
over voltage, over 
voltage at start 
•  The supply voltage is below 240VAC 
•  The supply voltage is unbalanced 
•  The deceleration time is too short 
•  The supply voltage is over 528 VAC 
(480V+10%), has over voltage spikes or 
not sinusoidal wave form 
•  Check that the supply voltage is not 
unbalanced 
•  Check that the supply voltage level is 
above 380VAC-15%. Use, for example, 
autotransformer to boost the voltage 
•  Set a longer deceleration time 
•  Measure the supply voltage level and 
wave form, use an autotransformer to 
lower the voltage 
•  Check the braking resistor cable (model 
006, not 003) 
•  Check the braking resistor type and 
resistance (internal 120Ω, external 90Ω) 
To reset: voltage must increase above the 
limit OR power off and restart after 1 min. 
Main voltage must be under 528 V
AC
  3 
Frequency converter 
Under / over temperature 
•  The crane is operated in a temperature 
that is too low/high 
•  The cubicle/panel heating is not working 
•  The cubicle/panel isolation is broken or 
the door is open 
•  The cubicle/panel cooling is not working 
•  Dust inside the frequency converter 
•  Broken cooling fan 
•  Check that the environment temperature 
meets the crane’s requirements 
•  Check the cubicle/panel heating/cooling 
systems and air flow. If cooling fan is not 
working replace the frequency converter. 
To reset: when the ambient temperature 
rises above -10˚C OR drops below +40˚C. 
  4 
Earth fault in motor 
output 
•  The motor load is not symmetric 
•  There is an insulation failure in the motor 
winding or motor cable 
•  Check the motor/motor cable insulation 
(phase-ground, phase-phase) 
To reset: power off and restart after 1 min 
  5 
External stop / limit 
warning 
•  Limit switch is activated 
•  The motor has overheated 
•  Loose or missing wire in DI6 
•  Parameter S5 setting 
•  Drive back from limit switch 
•  Wait until the motor is cooled down 
To reset: Power off and restart after 1 min. 
  6 
DC bus over voltage 
•  DC bus voltage has been too high 
because of too short slowdown ramp time 
•  The tailwind load is too high or, in tandem 
use, the other crane is pushing 
•  Check the braking resistor connection 
•  Increase the deceleration ramp time 
(Switch group S3) 
To reset: leave the controls at a neutral 
position at least 0.5 second 