11  TECHNICAL DATA 
Mains connection 
Supply voltage U
in 
380 - 480V, -15%...+10% 3-phase 
Supply voltage frequency  45…66 Hz 
Connection to mains  Once per minute or less (normal case) 
Motor connection  Output voltage  0 — 0,95*U
in
Nominal output current  003: I
N
 2.4A (max 3.6A), 006: I
N
 5.6A (max 7.7A) 
Continuous output current  Ambient temperature max. +50ºC, overload 1.5 x I
N
 (1min/10min) 
Starting current 
2 x I
N
 2 sec every 20 sec, if output frequency <30Hz and temperature 
of heatsink <+60ºC 
Output frequency  5…120 Hz (limited options) 
Braking resistor (only 006 
model) 
Resistance 
Internal resistor: 120 Ω (45 W continuous, 2000 W peak power) 
External resistor: 90 Ω (550W continuous power) 
Digital inputs  Control voltage  42 – 240 V
ac
, current consumption 15 ± 5 mA 
Terminals  Tightening torque  0,5 – 0,6 Nm 
Conductor diameter 
Mains, motor, braking resistor and grounding terminals: 1.5 – 4.0 mm 
Digital input terminals: 1.0 – 1.5 mm 
Control features  Control method 
Frequency Control U/f 
Open Loop Vector Control 
Switching frequency  3,6 kHz 
Field weakening point  Fixed values 
Acceleration time  1,5…5,5s (0,5s steps) 
Deceleration time  1,5…5,5s (0,5s steps) 
Ambient conditions  Ambient operating temperature  –10°C (no frost)…+50° C (outside the cubicle + 40˚C) 
Storage temperature  –40°C…+70°C 
Relative humidity  0…95% RH, non-condensing, non-corrosive, no dripping water 
Air quality: 
- Chemical vapors 
- Mechanical particles 
IEC 721-3-3, unit in operation, class 3C2 
IEC 721-3-3, unit in operation, class 3S2 
Altitude 
100% load capacity (no derating) up to 1000m. 1% derating for each 
100m above 1000m; max. 2000m 
Vibration: 
EN50178/EN60068-2-6 
5...150 Hz 
Displacement amplitude 1 (peak) mm at 5...15.8 Hz 
Max acceleration amplitude 1 G at 15.8...150 Hz 
Shock 
EN50178, IEC 68-2-27 
UPS Drop Test (for applicable UPS weights) 
Storage and shipping: max 15 G, 11 ms (in package) 
Enclosure class  IP20 
Weight  003 model: 0.6 kg, 006 model: 1.4 kg (including braking resistor) 
EMC  Immunity  Complies with EN61000-6-2, EMC: EN61800-3: 2004 
Emissions 
EMC-level N: with the internal EMC filter connected 
EMC level 0: with the internal EMC filter disconnected 
Complies with EN61800-3 A11 (2004) for second environment 
Safety 
61800-5-1, EN60204-1, CE, UL, cUL, FI, GOST R, IEC (see the unit’s 
main sticker for more detailed approvals), RoHS 
Protections 
Over voltage protection  875V
DC
 trip level 
Under voltage protection  333V
DC
 trip level 
Earth-fault protection 
Earth fault is tested before every start. In case of earth fault in motor 
or motor cable, only the frequency converter Is protected. 
Unit over temperature  Yes 
Motor stall  Yes 
Overcurrent protection  Trip limit 4,0*I
N
 instantaneously 
Motor overtemperature supervision  Yes 