Power class      002  003  004  005  007  011  015  018  022 
Continuous current  I
CONT
  A  6.5  8  10  13  18  24  32  42  48 
Fuse    A  10  10  10  16  20  25  35  50  50 
Max motor cable length    m  50  50  50  50  50  50  50  50  50 
    Ft  160  160  160  160  160  160  160  160  160 
Motor cable  40
o
C  mm
2
  1.5  2.5  2.5  2.5  4  6  10  10  10 
  104
o
F  AWG  14  14  14  12  10  10  8  8  6 
Braking resistor cable  40
o
C  mm
2
  2.5  2.5  2.5  2.5  2.5  2.5  2.5  4  4 
  104
o
F  AWG  14  14  14  14  14  14  14  12  12 
Power class      030  037  045  055 
Continuous current  I
CONT
  A  60  75  90  110 
Fuse    A  63  80  100  125 
Max motor cable length    m  50  50  75  75 
    Ft  160  160  240  240 
Motor cable  40
o
C  mm
2
  16  25  35  35 
  104
o
F  AWG  6  4  2  2 
Braking resistor cable  40
o
C  mm
2
  10  10  16  16 
  104
o
F  AWG  8  8  6  6 
1.11.4 Cable protection 
To protect the supply cables against short circuit there must be fuses or motor circuit breakers (MCCBs) installed at the 
mains end of the supply cable. Dimensioning of the fuses or MCCBs depends on the cable used and on the type of 
primary fuses or MCCBs. If there are no other regulations, the values given in this section can be used to dimension 
fuses (three phase 400V supply). 
The overload protection of inverter protects both the supply and the motor cables. The fuses of the supply provide the 
short circuit protection. 
1.11.5 Cable length 
The maximum motor cable lengths in the preceding table are based on 150% of inverter rated current (=current during 
acceleration) and a 2.5 % voltage drop in the cable. For longer cables, the required conductor cross sectional area A 
(mm2) is given by formula 
Up
Il
A
F
×
×
×
×=
5.1
43.2
where  l  is the cable length (m) 
  I
F
  is the motor current (A) at shaft power P
F
  p  is the allowed voltage drop in % 
  U  is the nominal motor voltage 
1.11.6 Du/dt filters 
If inverter is not mounted on the crane, there has to be du/dt filter at motor supply. Also if total motor cable length (sum of 
motor cables ) is over 100m with 002 –005 or over 200m with 007 –055, there has to be du/dt filter at motor supply. 
Power class  Platthaus du/dt filter  Length (mm)  Width (mm)  Height (mm)  Weight (kg)  ID 
002 – 003  ULC-910-920  100  110  180  1.2  52306553 
004 – 005  ULC-914-931  125  110  200  3  52306554 
007 – 018  ULC-918-951  155  125  225  7  52306555 
022 – 045  ULC-923-927  190  135  260  12  52306556 
055  ULC-942-1044  240  175  310  22  52306557 
m Du/dt filter should be as near inverter as possible 
m Note! All control cables must be placed as far from the motor and braking resistor 
cables as possible. 