1.17.2 ESD141 
Brake control unit ESD141 is a line voltage full/half-wave rectifier for DC-brakes. 
123
4
5
6 7
K7
K7
Set 0.3s
Brake
K7
K7
ESD141
AC Line Voltage
K7
Voltage range  200...690Vac   
Output voltage U
DC
Full wave 0.90 x U
AC
Half wave 0.45 x U
AC
Maximum current  1.25Adc continuous and 2.5Adc at ED5%   
When the brake is opened, the brake contactor K7 connects two phases of mains 
voltage to terminals 1, 2 and 3, which makes the device a full wave rectifier. The full 
wave mode is used to get the brake open fast. In addition, the brake contactor shorts 
terminals 4 and 5 thus making the DC-circuit. 
After a time delay (normally 0.3s), the delayed contact of the brake contactor opens, 
which disconnects the supply from terminal 3 and the rectifier changes to a half wave 
type. Half wave operation prevents heating of the brake coil and is enough to keep the 
brake open.
To close the brake, the brake contactor disconnects the supply to terminals 1 and 2. The released brake contactor also 
opens the brake coil DC-circuit, which speeds closing of the brake. The purpose of the varistor there is overvoltage 
protection for K7 contacts and the brake coil. 