2.10  Optic cable connections 
Synchronization between 2 hoists  Synchronization between 4 hoists 
Hoist A 
Address 
P2.4.1=1 
Next Address 
 P2.4.2=2 
Last Address  
P2.4.3=2 
Hoist B 
Address 
P2.4.1=2 
Next Address  
P2.4.2=1 
Last Address  
P2.4.3=2 
Hoist A 
Address  
P2.4.1=1 
Next Address  
P2.4.2=2 
Last Address  
P2.4.3=4 
Hoist B 
Address  
P2.4.1=2 
Next Address  
P2.4.2=3 
Last Address  
P2.4.3=4 
Hoist C 
Address  
P2.4.1=3 
Next Address  
P2.4.2=4 
Last Address  
P2.4.3=4 
Hoist D 
Address  
P2.4.1=4 
Next Address  
P2.4.2=1 
Last Address  
P2.4.3=4 
H1 H2  H3 H4 H1 H2 H3 H4
H1 H2 H3 H4 H1 H2 H3 H4
H1 H2 H3 H4 H1 H2 H3 H4
H1 H2 H3 H4 H1 H2 H3 H4
H1 H2 H3 H4 H1 H2 H3 H4
H1 H2 H3 H4 H1 H2 H3 H4
2.11  Troubleshooting 
Should problems arise with the Synchro, first check that all drives function correctly without synchronization being 
activated. 
Problem  Possible cause  Checking 
Synchro functions normally, V2.4.10.1 
(master) does not show position error, 
but between hooks there comes 
position error. 
System does not register position error 
between hooks because P2.2.2. Nominal 
Speed in one or more drives is not correct or 
accurate enough. 
Check P2.4.4 Nominal speed in all drives. 
One or more drives are vibrating 
especially after acceleration or 
deceleration. 
Too high gain level. Speed correction is 
overshooting. 
Reduce P2.4.6. SystemBus Synchro gains 
value in master drive. 
Position error between hooks, 
especially after acceleration, 
deceleration or stopping. 
Different ramp times or stop function.  Check that Ramp time and Stop method 
parameters P2.1.10, P2.1.11 and P2.2.20 
have similar value in every drive. 