•  S3 = Both EA+/- and EB+/- are missing 
•  S4 = EA+/- and EB+/- are crossconnected
• 
S5 = SSU-board is missing or system load is 
too high 
•  Encoder type and pulse number 
F44  Device changed
Option board or control unit has been 
changed to different type or different power 
rating 
Reset the fault. Option board parameters or all parameters 
are set up to default values. 
  X 
F45  Device added  Option board of different type or drive of 
different power rating added. 
Reset the fault. Option board parameters or all parameters 
are set up to default values. 
  X 
F50  Reference 
value fault 
Analog input signal is out of selected range 
1-9V or 2-10V 
•  Control cable is broken 
•  Signal source has failed 
Check: 
•  Reference cable 
•  Reference source 
  X 
F 51  Stop limit  Stop limit has tripped  Reset: keep controller at zero >300ms. 
Ensure that fault disappears after leaving the stop limit. 
X
F 55  Board Fault  Some of following board is missing: 
•  A = Basic I/O board 
•  B = Thermistor board 
•  D = Expansion board 
Reset: switch power off and restart after the lamps of 
keypad are off. 
Check: 
•  board slots A, B and D 
•  drive selection 
•  control mode 
  X 
F 56  Generator side 
current limit 
Too short deceleration time 
•  generator side current limit 
Reset has an additional 5 s time delay. 
Check: 
•  deceleration time 
  X 
F 57 
Thermistor fault
Thermistor input in relay / thermistor board 
has detected motor overtemperature. Fault 
appears when thermistor input has been 
open over 1s. 
Check: 
•  motor cooling and loading 
•  thermistor connection. If expansion board thermistor 
input is not used, it should be shorted 
•  motor parameters 
•  the brake operation 
X
F 60  Parameter fault
Inverter has lost parameters. Drive selection 
parameter has changed to 0 / none. 
Download parameters from keypad    X 
F 61  Overspeed Fault  SSU has tripped to Overspeed (hardware 
supervision). Motor speed has increased 
above overspeed detection level. 
Reset: switch power off and restart after the lamps of 
keypad are off. 
Check: 
function and cabling 
maximum frequency setting parameters 
SSU settings 
  X 
F 62  Speed Difference 
Fault 
SSU has tripped to Speed Difference  Reset: switch power off and restart after the lamps of 
keypad are off. 
Check: 
pulse sensor/encoder function and cabling 
pulse sensor/encoder pulse number 
speed difference supervision settings 
  X 
F 63  Stall Supervision 
Fault 
SSU has tripped to Stall.  Reset: switch power off and restart after the lamps of 
keypad are off. 
Check: 
brake operation 
pulse sensor/encoder function and cabling 
stall supervision settings 
  X 
F 64  SSU Relay Test 
Fault 
Relay in SSU board is damaged or SSU 
relay is bypassed 
Reset: switch power off and restart after the lamps of 
keypad are off. 
Check: 
ES and RDY external connections 
OK input operation 
change SSU board 
  X 
F 65  SSU Watchdog  SSU internal fault 
interference fault between SSU board and 
control board 
component failure (control board or SSU 
board) 
Reset: switch power off and restart after the lamps of 
display are off. 
Check: 
SSU status (System menu / System info / Expander 
boards / C: SSU / status) 
SSU LED’s 
If the fault comes again, contact service 
  X 
F 66  SSU Overspeed 
Limit 
SSU overspeed limit has been set over 
140% of maximum frequency 
Check: 
set SSU overspeed limit under 140% of maximum 
frequency 
  X 