INSTALLATION
WARNING!
This product is intended for industrial use. In a domestic environment this product may cause radio
interference. It is the users responsibility to take adequate precautions.
Placing
Position the welding power source such way that its cooling air inlets and outlets are
not obstructed.
Mains power supply
Check that the unit is connected to the correct mains power supply voltage, and that
it is protected by the correct fuse size. A protective earth connection must be made,
in accordance with regulations.
Rating plate with supply connection data
Caddy
R
RR
R
Mig C160i 1 50/60 Hz
Voltage V 230±15%
Current A
at 100% duty cycle 10
at 60% duty cycle 12.8
at 35% duty cycle 17.5
Cable area mm
2
22
2
3 x 1.5
Fuse slow A 16
NB: The mains cable areas and fuse sizes as shown above are in accordance with Swedish
regulations. They may not be applicable in other countries: make sure that the cable area and fuse
sizes comply with the relevant national regulations.
PFC
The machine is equipped with Power Factor Correction converter and has
near--to--unity power factor. It complies with standard EN 61000--3--12:2005--04
Electromagnetic compatibility (EMC) -- Part 3--12: Limits for harmonic currents
produced by equipment connected to public low--voltage systems with input
current > 16 A and <= 75 A per phase.
Extension cord
If extension cord is needed it is recommended to use cord 3x2,5mm
2
of maximum
length 50m.