English TABLE OF CONTENTS Enterprise Series Owner's Manual 1. Introduction 2 2. Controls and Indicators 4 3. Installation 5 4. Operation 9 5. Troubleshooting 11 6. Replacing the Battery 12 7. Obtaining Service 14 8. Specifications 15 9. Configurable Parameters & Settings 16 10. Limited Product Warranty 18 11. Declaration of Conformity 19 © Copyright Para Systems, Inc.
English INTRODUCTION Thank you for purchasing a MINUTEMAN power protection product. It has been designed and manufactured to provide many years of trouble free service. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS ! Please read the manual before installing your Enterprise Series UPS. It provides the information that should be followed during installation and maintenance of the UPS and the batteries allowing you to correctly set up your system for the maximum safety and performance.
PLEASE SAVE THE PACKING MATERIALS! WARNING: RISK OF ELECTRICAL SHOCK. HAZARDOUS LIVE PARTS INSIDE THIS POWER SUPPLY ARE ENERGIZED FROM THE BATTERY EVEN WHEN THE AC INPUT POWER IS DISCONNECTED. TO DE-ENERGIZE THE OUTPUTS OF THE UPS: 1. IF THE UPS IS ON PRESS THE ON/OFF BUTTON FOR 1 SECOND 2. DISCONNECT THE UPS FROM THE AC POWER OUTLET 3. TO DEENERGIZE THE UPS COMPLETELY, DISCONNECT THE BATTERY.
English CONTROLS AND INDICATORS FRONT PANEL On-Line/On-Battery/Boost/Buck LED Fault LED Overload LED Weak/Bad Battery LED Site Wiring Fault LED On/Off/Test Switch Press and release the ON/OFF/TEST button after one beep to turn the unit ON or OFF (see section 4) On-Line On-Battery Buck Boost The On-Line/On-Battery/Boost and Buck (green) LED illuminates in a steady state when the UPS is on and supplying AC power to the load.
5 7 3 English 6 10 2 1 9 8 REAR PANEL (120Vac models shown) 1. The computer interface port is for the UPS monitoring and control. (see section 3) 2. The RJ-45/RJ-11 modular connectors are used for 10 Base-T network/single line telephone surge protection. (see section 3) 3. The output receptacles are NEMA 5-15R type. (IEC output sockets on 230Vac models) 4.
INSTALLATION English Be sure to read the installation placement and all the cautions before installing the UPS. The Enterprise series UPS has external Battery Pack capability, please observe the following warning when connecting the Battery Pack(s). WARNING! DO NOT PLUG THE BATTERY PACK'S POWER CORD INTO THE UPS's OUTPUT RECEPTACLES, DAMAGE TO THE BATTERY PACK'S INTERNAL CHARGER MAY OCCUR.
English The Tower Configuration allows the user to install the UPS in the up-right position next to the tower computer. There is a tower bracket kit available for the UPS. Use CAUTION, the UPS is extremely heavy. Once the location of the UPS has been determined, lay the UPS down flat on a desk or a table. Position the UPS so that the tower brackets will slide on the unit.
English The Rackmount Configuration comes with mounting brackets for the standard 19" (46.5cm) rack. The mounting brackets to fit a 23" (59.2cm) standard rack are also available. The screws for mounting the UPS to the rack are not included (screw size varies with rack size). The kit includes, two mounting brackets and eight retaining screws. Locate the mounting bracket screw holes on the side panels of the UPS, at the front of the UPS. Align the mounting bracket with the mounting bracket screw holes.
CHECKING THE SITE WIRING FAULT (120Vac models only) English After plugging in the UPS, check the Site Wiring Fault (SWF) LED on the front panel of the unit. If the LED is illuminated the UPS is plugged into an improperly wired AC outlet. CAUTION! IF THE UPS INDICATES A SITE WIRING FAULT, HAVE A QUALIFIED ELECTRICIAN CORRECT THE PROBLEM.
DIP SWITCH SETTINGS English The DIP Switch setting may be changed by the user to set the desired inverter (on battery) output voltage. The DIP Switch must be set to the desired output voltage and then the unit must be turned OFF and restarted to reconfigure the microprocessor and save the change. The setting for the 117Vac units may be 108Vac, 113Vac, or 117Vac. This setting will adjust the inverter (on battery) output voltage only. The setting for the 225Vac units maybe 215Vac, 225Vac, and 235Vac.
Symptom English # TROUBLESHOOTING Possible Cause What To Do UPS will not turn on On / Off / Test button not pushed Press the On button momentarily, (one beep) to start UPS UPS operates in battery mode only, even though there is normal AC present Input AC circuit breaker is tripped Reset circuit breaker by pressing the plunger back in.
English $ REPLACING THE BATTERY REPLACING THE BATTERY The Enterprise Series UPS has an easy to replace hot-swappable battery(s). Please read the following warning statements before attempting to service the battery(s). NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up. WARNING! THIS UNINTERRUPTIBLE POWER SOURCE CONTAINS POTENTIALLY HAZARDOUS VOLTAGES.
PLEASE READ THE CAUTIONS BEFORE ATTEMPTING TO REPLACE THE BATTERIES Hot-swappable batteries means that the batteries can be replaced without powering down the whole UPS system. NOTE: If there is a power interruption while replacing the hotswappable batteries, with the UPS on, the load will not be backed up. NOTE: To Hot-Swap, skip to step number 6. 1. Turn off the equipment that is plugged into the output receptacles of the UPS. 2. Press and release, after one beep, the ON/OFF button on the front panel. 3.
English % OBTAINING SERVICE IF THE UPS REQUIRES SERVICE 1.Use the TROUBLESHOOTING section to eliminate obvious causes. 2.Verify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem. 3.Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve the problem call or fax MINUTEMAN Technical Support at the following numbers; Voice phone (972) 446-7363, FAX line (972) 446-9011 or visit our Web site at www.minutemanups.
NOTE: 230Vac Specs Shown In ( ) 500VA 750VA 1100VA Acceptable input voltage 1500VA 2300VA Input voltage (on-line operation) 75 - 164 (150 - 290) Vac Output voltage 105 - 128 (210 - 250) Vac Nominal input frequency 50 or 60 Hz, autosensing Input protection Resettable circuit breaker Frequency limits (on-line operation) 50 or 60 Hz, +/-6Hz Transfer time Maximum load 500VA On-battery frequency 1100VA 750VA 660W 450W 3200VA 2300VA 900W 50 or 60 Hz, +/-.
English ' CONFIGURABLE PARAMETERS AND SETTINGS (These items require optional software or hardware) FUNCTION FACTORY DEFAULT USER CHOICES DESCRIPTION UPS ID Enterprise Series Up to 64 characters to Use this function to uniquely identify the UPS in your netdefine the UPS work configuration Battery install date Date of manufacture Date of battery re- Enter the current date when replacing batteries placement day/month/year XX/XX/XXXX Battery life in days 1826 Up to 5 characters At first battery
English Customized Output Receptacle Panels The Enterprise series UPS has a removable receptacle panel. The receptacle panel can be configured with one locking receptacle and two duplex receptacles. This will allow the user to customize the output receptacles for their specific applications. MINUTEMAN will only use UL or CE approved receptacles. Here is one example that could be used: one L530R, one 5-15R duplex and one 5-20R duplex.
English LIMITED PRODUCT WARRANTY LIMITED PRODUCT WARRANTY Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of manufacture. For equipment sites within the United States and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center.
English DECLARATION OF CONFORMITY Application of Council Directive(s): 89/336/EEC, 7/23/EEC Standard(s) to which Conformity is declared: EN50091-2, EN60555-2, EN61000-3, EN50091-1 Manufacturer’s Name: Para Systems, Inc.
English Notes: 20