Specifications
Chapter  4 Configuration  Installation and Operation Manual 
4-16  Performing Additional Tasks  Optimux-108 Ver. 6.1 
Displaying the System Status    
The System Status screen displays the current status of the local or remote 
Optimux-108 units. 
Table 
4-7
 lists the values and the meaning of these 
parameters. 
Optimux-108 
Monitoring>System>Status 
1. Device Number > (Local) 
 Device Type > (Optimux-108) 
 Force Link > (LINK A) 
 Active Link > (LINK A) 
 Redundancy Status > (Available) 
 Redundancy Mode > (Auto) 
 PS A status > (OK) 
 PS B status > (OK) 
 Alarm Indication > (Major) 
 Test Indication > (Off) 
> 
Please select item <1 to 1> 
ESC-Previous menu; !-Main Menu; &-Exit        1 User(s) 
Figure 
4-20. System Status Screen 
Table 
4-7. System Status Parameters 
Parameter Description 
Device Number 
Indicates the Optimux-108 currently being monitored: 
•  Local 
•  Remote 
Device Type  Displays the device type 
Redundancy Status  Indicates if redundancy is available or not available 
•  Available – two uplinks are installed 
•  Not Available – only one uplink is installed, or Redundancy 
mode is ‘OFF’ 
Redundancy Mode  The redundancy state of the system: 
•  Auto 
•  Manual 
•  Off 
The option is hidden when redundancy status is not available. 
Force Link  Indicates the main uplink 
Active link  Identifies the currently active link 
PS A Status  The state of Power Supply A: 
•  OK 
•  Fault 
•  Not mounted (in case only one PS has been ordered – PS B) 