Specifications
  Accessing and Exiting the Supervisory Terminal  4-1 
Chapter 4 
Supervisory Port Software 
Configuration 
4.1 Introduction 
The Optimux-XLT1 parameters can be configured from a supervisory terminal 
connected to the unit's CONTROL/MNG connector. Remote management is also 
possible using the Telnet communication protocol through the unit’s MNG-ETH 
connector. 
All the example screens shown in this chapter are for different hardware/software 
situations that are available. 
4.2  Accessing and Exiting the Supervisory Terminal 
➤  To access the supervisory terminal for configuration: 
1.  Connect an ASCII ANSI terminal, or a PC capable of emulating an ASCII ANSI 
terminal, to the 25-pin CONTROL/MNG connector on the rear panel of the 
Optimux-XLT1 (for the cable wiring diagram, refer to the Control Cable Wiring 
figure). 
2.  Set the terminal communication parameters to: 19,200 baud, 8 bits/character, 
one stop bit and no parity bit. 
Optimux-XLT1 automatically detects and adapts itself to terminal baud rates of 
9600, 19200, 38400, 57600 and 115200 bps only. 
3.  Turn the unit on and immediately press <Enter> four or more times. If the 
correct baud rate was detected, dots will start to appear correctly on the 
terminal screen. 
4.  Press the dot <.> key once to set the parity and to complete the detection. 
This baud setting will be saved in non-volatile RAM. 
If the auto-detection fails, the baud rate of the Optimux-XLT1 management 
port is the last baud rate that was written in the non-volatile RAM. 
5.  If a PC is used, run a terminal emulation program. 
6.  Reset the Optimux-XLT1 or turn it ON. 
The Optimux-XLT1 Main Menu appears. 
Note 
Order from: Cutter Networks
Ph:727-398-5252/Fax:727-397-9610
www.bestdatasource.com










