Datasheet

SPPC - LJP
25
Characteristics
LUG-IT - Power cable joining system
Lugit is a safe and efficient means to make temporary
connection / extensions of single core power cables
that are pre-terminated with copper lug terminals.
APPLICATIONS
Power distribution
Utilities
Electric Vehicles
Railway Equipment
Military Field Power
Mobile Generators
Loadbanks
Back-up Power Systems
Key characteristics
Increase cable utilization
Reusable
Suitable for temporary connections
Standardize on cable lengths held in stock
Decrease cable purchase
Reduce transportation of cables between sites
No need for connectors or junction boxes
Daisy chain hook up system
Details
IP67 Protected when assembled.
Nominal Voltage Un: 1000Vac
2 Lug-it sizes available according to the lug and cable dimensions:
o LJP-120 from 35mm² up to 120mm²
o LJP-300 from 150mm² up to 300mm².
Insulating voltage: 5.000Vac
Rated current (to be checked with the specific cable characteristics):
o Lugs 120 mm
2
:350A (30°C)
o Lugs 185 mm
2
:570A (30°C)
o Lugs 240 mm
2
:670A (30°C)
o Lugs 300 mm
2
:780A (30°C)
Working temperature: -30°C ÷ +120°C
Protection degree: IP67 (EN 60529)
Audible and tactile indication of locking
Secure lock for unwanted / unauthorised release
Quick assembly in approx. 2 minutes without special tools. The system can be disassembled and reused