CT102 Thermostat
Z Wave
®
Conguration Parameters
This device supports the following Conguration Parameters:
Name Set/Get Default Values
1 Temp Reporting Threshold Set/Get 2 0 to 4
2 HVAC Settings Get Only N/A see below
3 Utility Lock Enable/Disable Set Only 0 0 to 127
4 C- Wire/Battery Status Get Only N/A 0 or 1
5 Humidity Reporting Threshold Set/Get 2 0 to 3
6 Auxiliary/Emergency Set/Get 0 0 or 1
7 Thermostat Swing Temp Set/Get 2 1 to 8
8 Thermostat Di Temp Set/Get 4 4 to 12
9 Thermostat Recovery Mode Set/Get 2 1 or 2
10 Temp Reporting Filter Set/Get see below
11 Simple UI Mode Enable/Disable Set/Get 1 0 or 1
12 Multicast Enable/Disable Set/Get 0 0 or 1
1. Temperature Reporting Threshold (8-bit)
This value determines the reporting threshold when association
reporting is enabled. Unsupported values are ignored.
Value
0 1 2 3 4
Treshhold
Disabled Disabled 0.5°F 1.0°F 1.5°F
2. HVAC Settings (32-bit)
Byte 1 = HVAC Setup: Normal (0x01) or Heat Pump (0x02)
Byte 2 = Aux Setup (Gas (0x01) or Electric (0x02)) & Number of
Auxiliary Stages (Heat Pump)/Number of Heat Stages
(Normal)
Byte 3 = Number of Heat Pump Stages
Byte 4 = Number of Cool Stages
3. Utility Lock (8-bit)
If set to 0, the utility lock is disabled. All other values (1-255) enable
the utility lock.