CT102 Thermostat
Z Wave
®
4. C-Wire/Battery Status (8-bit)
If 0x01, the thermostat is powered by a C-wire. If 0x02, the
thermostat is powered by batteries.
5. Humidity Reporting Threshold (8-bit)
This value determines the reporting threshold when association
reporting is enabled. Unsupported values are ignored.
6. Auxiliary/Emergency (8-bit)
If set to 0, auxiliary / emergency heat is disabled. All other values
(1-255) enable auxiliary / emergency heat. This can only be
enabled when the thermostat is set to Heat Pump mode.
7. Thermostat Swing Temp
The thermostat swing temperature is in units of 0.5 degrees
Fahrenheit. A value of 0x01 is 0.5F and 0x02 is 1.0F. The supported
values may vary from thermostat to thermostat but typically the
allowed values are 0.5F (0x01) to 4.0F (0x08).
8. Thermostat Di Temp
The thermostat dierential temperature is in units of 0.5 degrees
Fahrenheit. A value of 0x04 is 2.0F and 0x06 is 3.0F. The dierential
temperature must be an integer value. Non-integer values, such
as 1.5F (0x03), should not be used. The supported values may vary
from thermostat to thermostat but typically, the allowed values are
2.0F (0x04) to 6.0F (0x0C).
9. Thermostat Recovery Mode
The Thermostat Recovery Mode can be either fast (0x01) or
economy (0x02).