User's Manual

MC-Series ©2008 RadioFrame Networks, Inc. 2-3
Proprietary and Confidential Information
MC-Series Standard Capacity system998-1019-01 Rev X1
Table 2.3 Power Requirements
2.3.2 Power Consumption
Table 2.4 Power Consumption per Assembly (See Note)
Note: Panduit termination lugs are required for
installation. Wire size is AWG 6.
2.3.3 Grounding
Table 2.5 Grounding Resistance (See Note)
Note: Panduit termination lugs are required for
installation. Wire size is AWG 6.
Ground included with enclosure on main ground
block.
Supplier Component Power
RadioFrame Networks
ABIC
–48 VDC
DRBS
–48 VDC
RF Shelf
–48 VDC
PDU
–48 VDC
Non-RadioFrame Networks
iSCIII
–48 VDC
EAS
–48 VDC
CSU
–48 VDC
Assembly Qty
Power per
Assembly (W)
Total Power
(W)
Current
(A
@ –48 VDC)
RF Shelf 1
DRBS (8 RadioBlade transceivers per) 3
ABIC 1
RadioFrame Networks Equiment
Total 1483 30.9
iSCIII 2
EAS 1
CSU 1
Non-radioframe Networks Equipment Total 105.6 2.2
TOTAL
1588 33.1
Supplier Component
Ground Resistance
(mOhms)
RadioFrame Networks
Cabinet 0.6