Installation guide
D6600/D6100 | Operation and Installation Guide | 9.0  Input and Output Ports 
16  Bosch Security Systems | 4/05 | 4998122704F 
9.1  UPS Monitoring through CPU 
Programmable Input Ports 
Use the CPU programmable input port to connect the 
external UPS to the D6600/D6100 for power 
monitoring. Connect the monitoring port from the UPS 
to matching pins on the D6600/D6100 CPU 
Programmable Input/Output port (Figure 14). Wiring 
must run from the receiver through the UL Listed rack, 
exit the rack through a conduit connection, and 
terminate at the external UPS for UL applications. Set 
up the D6600/D6100 from Menu 2.2.27 CPU 
Programmable Input 1 for Input 1; Menu 2.2.28 
CPU Programmable Input 2 for Input 2. Refer to the 
D6600/D6100 Program Entry Guide (P/N: 4998122702) 
for more information. 
9.1.1  Input Default Connection Configuration 
•  The I/O ports work with dry contact outputs. 
•  The open circuit input voltage on the input 
measures between 9 V and 12 V. 
•  UPS Battery OK (restore) – contacts closed 
•  UPS Battery Low input – contacts open 
You can apply other output sources to the input wiring 
as long as you follow these guidelines: 
•  The maximum input voltage allowed without 
causing damage to the input is 24 VDC. 
•  For UPS “Battery OK” (restore), the input range 
must be between 0 V and 1 V. 
•  For UPS “Battery Low,” the input range must be 
between 3 V and 24 V. 
Because the input state is undefined in 
the voltage range, input voltages between 
1 V and 3 V can cause abnormal results. 
This might cause unexpected results such 
as toggling between “Battery Low” and 
“Battery OK.” 
9.1.2  Input Reverse Connection Configuration 
If the input must be the opposite polarity for correct 
operation, place an external transistor circuit between 
the UPS output signal and the D6600 I/O input 
(Figure 16). 
Follow these guidelines for correct operation: 
•  The maximum input voltage allowed without 
damaging the input is 24 V. 
•  UPS Battery OK (restore) input range from the 
UPS operates between 5 V and 24 V. 
•  UPS Battery Low input range operates between 
0 V and 0.5 V 
Figure 16:  Input Wiring for Reverse Configuration 
1
2
3
5
4
1 – From UPS Battery OK signal 5 to 24 V 
2 – 22 k to 39 k 
3 – Battery Low signal 0 to 0.6V 
4 – To I/O input 
5 – Any general purpose NPN transistor 
Operating the input as an analog input 
between 0.5 V and 5 V might cause 
abnormal results. This input state is not 
defined and might change expected 
results 
Reverse configuration is not for use in UL 
Listed applications. 
9.2  Automation Link Monitoring (COM3) 
through CPU Programmable Output 
Ports 
The output connections on the I/O port have an open 
collector transistor output that can activate an external 
sounder or light if the automation system fails. 
Configure external devices using the 
specifications listed in Table 9. Outputs 
are not verified by UL. 
Table 9:  Terminator Card Configuration 
Radionics D6615 CPU 
Terminator Card 
Bosch D6615 CPU 
Terminator Card 
Solid state output provides 
a current sink to common (-) 
Solid State output provides 
a current sink to common (-) 
Maximum load is 20 mA  Maximum load is 75 mA 
Vsat @ 1 mA = 0.5 VDC  Vsat @ 10 mA = 0.5 VDC 
Vsat @ 10 mA = 3.0 VDC  Vsat @ 25 mA = 1.0 VDC 
Maximum voltage = 30 VDC  Vsat @ 50 mA = 2.5 VDC 
  Maximum voltage = 30 VDC 










