Installation guide
D6600/D6100 | Operation and Installation Guide | 16.0 Specifications 
34  Bosch Security Systems | 4/05 | 4998122704F 
16.0 Specifications 
Table 12: D6600/D6100 Specifications 
Rack mount (2U) 
18 cm x 48.3 cm x 49.5 cm 
(7.0 in. x 19.0 in. x 19.5 in.) 
D6600 
Standalone 
18 cm x 45.0 cm x 49.5 cm 
(7.0 in. x 17.75 in. x 19.5 in.) 
Rack mount (1U) 
9.0 cm. x 37.5 cm. x 25.5 cm 
(3.5 in. x 19 in. x 10 in.) 
Dimensions 
(H x W x D) 
D6100 
Standalone 
9.0 cm. x 30.5 cm. x 25.5 cm 
(3.5 in. x 12.0 in. x 10 in.) 
D6600  8.7 kg (19 lb) 
Weight 
D6100  3 kg (7 lb) 
Cabinet Finish 
Aluminum, dark gray, semi-gloss enamel. 
AC Nominal Operating Range  120 V or 230 V 
Power Input 
AC Maximum Operating Range 
100 VAC to 120 VAC, 220 VAC to 230 VAC, 50/60 Hz 
2.5 A maximum 
Required battery current  800 mA D6600 with one line card installed 
Required UPS AC standby current  350 mA 
Required additional battery current  210 mA 
For each additional line card or terminal 
card pair 
Required additional UPS AC standby current  35 mA 
Required additional battery current  10 mA For network communications card 
Required additional UPS AC standby current  10 mA 
Required battery current  330 mA 
Current Required 
D6100 
Required UPS AC standby current  180 mA 
Standby Power 
Use a UPS with the D6600/D6100. The receiver includes an external battery connection and battery harness. Use 
12 V rechargeable sealed lead-acid batteries. A 4-hour minimum standby power supply (UPS or battery) is required 
for UL Certification (refer to Section 8.1 Connecting External Batteries on page 14 for battery size). 
Telephone 
RJ11C modular jacks, with 26 AWG or larger wire diameter. 
ESVUSA-25328-AL-N 
The D6600 Receiver is Federal Communications Commission (FCC) registered under Part No. 68 using the 
RJ11C Interconnect that can be ordered from your local telephone company. 
FCC Registration 
Notice:  This equipment was tested and found to comply with the limits for a Class “A” digital device, pursuant to 
Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference 
when operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency 
energy, and if not installed according to the instruction manual, might cause harmful interference to radio 
communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which 
case the user must correct the interference at his or her own expense. 
Ringer Equivalence 
0.4 B 
Screen size: (H x W)  0.7 in. x 6.0 in. (1.8 cm x 15.2 cm) dot matrix LCD (5 x 7 dots per character). 
Shows two separate lines of 40-characters each. 
Display 
LED  LED display section indicates receiver status and power. 
Inputs and Outputs 
•  One RS-232 interface port COM3 (middle connector on the CPU terminator card) for connection to an 
automation computer. 
•  One RS-232 interface port COM4 (upper connector of CPU terminator card) for connection to an external 
serial printer, a PC, a modem, or a network. 
•  One parallel printer port for connection to a parallel printer 
•  Two programmable inputs (wire harness included) 
•  Two programmable outputs (wire harness included) 
•  Optional: One RS-232 port (COM1) for the Network Communications expansion option (D6600 only). 
•  Austel Approved 
•  CE Approved 
- CTR-21 
- EN60950 Safety 
-  EN55022 Radiated/ 
Conducted Emissions 
Listings and 
Approvals 
(D6100 Listings and 
Approvals are 
pending) 
•  UL Central Station Fire (864) 
•  UL Central Station Burglary (1610) 
•  UL Police Station Connect (365) 
•  FCC Part 15 Radiated/Conducted Emissions 
•  FCC Part 68 Telecom 
•  ULC 
•  Industry Canada 
•  NIST AES Certification 