Specifications

B
IPMI Commands and Managed Sensors
130
10h IOH Die Temp Minor temperature
high
Temperature over -20 threshold. Monitor to see if the alarm worsens.
Major temperature
high
Temperature over -13 threshold. Monitor to see if the alarm worsens or is persistent
for more than 1 hour. If persistent, remove and/or hot
swap CPM. If problem persists, remove CPM and
contact customer support.
Critical temperature
high
Temperature over -1 threshold.
Most Shelf Managers shut down
the CPM.
Remove and/or hot swap CPM. If problem persists,
remove CPM and contact customer support.
Minor temperature
low
N/A N/A
Major temperature
low
N/A N/A
Critical temperature
low
N/A N/A
11h CPU Core DTS Minor temperature
high
Temperature over -20 threshold. Monitor to see if the alarm worsens.
Major temperature
high
Temperature over -13 threshold. Monitor to see if the alarm worsens or is persistent
for more than 1 hour. If persistent, remove and/or hot
swap CPM. If problem persists, remove CPM and
contact customer support.
Critical temperature
high
Temperature over -1 threshold.
Most Shelf Managers shut down
the CPM.
Remove and/or hot swap CPM. If problem persists,
remove CPM and contact customer support.
Minor temperature
low
N/A N/A
Major temperature
low
N/A N/A
Critical temperature
low
N/A N/A
12h CPU ThermTrip N/A CPM over temperature event Check other CPU Temp sensors. Remove and/or hot
swap CPM. If problem persists, remove CPM and
contact customer support.
Table 38. Sensor alarms and recommended actions (sheet 6 of 14)
Number Name Alarm level Possible errors or faults Recommendation