Specifications

B
IPMI Commands and Managed Sensors
134
1Fh +1.8V_CPU Minor voltage high Voltage over 1.89V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage high Voltage over 1.98V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage high Voltage over 2.07V threshold;
CPM will not go into M4 state.
1
Remove CPM and contact customer support.
Minor voltage low Voltage under 1.71V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage low Voltage under 1.62V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage low Voltage at 0V threshold; CPM will
not go into M4 state.
1
Remove CPM and contact customer support.
20h +1.8V_BASE Minor voltage high Voltage over 1.89V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage high Voltage over 1.98V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage high Voltage over 2.07V threshold;
CPM will not go into M4 state.
1
Remove CPM and contact customer support.
Minor voltage low Voltage under 1.71V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage low Voltage under 1.62V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage low Voltage at 0V threshold; CPM will
not go into M4 state.
1
Remove CPM and contact customer support.
21h +1.8V_FRONT Minor voltage high Voltage over 1.89V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage high Voltage over 1.98V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage high Voltage over 2.07V threshold;
CPM will not go into M4 state.
1
Remove CPM and contact customer support.
Minor voltage low Voltage under 1.71V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage low Voltage under 1.62V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage low Voltage at 0V threshold; CPM will
not go into M4 state.
1
Remove CPM and contact customer support.
Table 38. Sensor alarms and recommended actions (sheet 10 of 14)
Number Name Alarm level Possible errors or faults Recommendation